Pogo Test
Penetration Test for Foamed Concrete
Introduction
Before a foamed concrete trench
reinstatement may be satisfactorily
surfaced with a bituminous base and
wearing course, the foamed concrete
must have sufficient strength to allow
the full compaction of these surface
layers.
The HAUC Specification for the
excavation and reinstatement of openings
in highways recommends the use of a
simple penetration or indentation test to
confirm that the reinstatement has
gained adequate strength before
surfacing begins.
No strength requirement is stipulated in
the HAUC specification; however site
tests have shown that satisfactory
compaction of the bituminous material
can be achieved once the foamed
concrete has developed an indicated
compressive strength of 1 N/mm squared
The 'Pogo' Tester is a simple, non-
electronic site tester which will indicate
when a foamed concrete trench
reinstatement is ready to be surfaced.
Operation
Before testing, the reinstatement area
selected should be cleared of any loose
material, dust etc..
The spring-loaded plunger at the base
of the tester is pressed manually onto
the surface to be checked until the red
indicator appears at the top of the tube
VVhen this can be done without
producing a significant indentation
( less than 1 mm ) in the foamed
concrete, the reinstatement has gained
a nominal strength of at least 1 N/mm squared
Indentation depths between 2 and 5
mm are likely to be formed in material
with a cube crushing strength of 0.5
N/mm squared.
The 'Pogo' Tester should , however, be
regarded as a go/no-go gauge. No
attempt should be made to estimate the
strength of the foamed concrete from
the depth of any indentation.
Specification
Weight : 1.8 kg
Length: 850mm
Downward force required: (112 Ibf)
|